Main Technical Specification
|
Type
|
|
|
TF310A
|
|
|
VOLTAGE RATINGS AT RATED CONTACT STROKE
|
|
1
|
Rated frequency
|
Hz
|
50
|
|
|
2
|
Rated Voltage
|
kV
|
12
|
|
|
3
|
Rated short-time power-frequency withstand voltage (1 min)
|
kV
|
42
|
|
|
4
|
Rated lightning impulse withstand voltage
|
kV
|
75
|
|
|
CURRENT RATINGS
|
|
|
1
|
Rated Current
|
A
|
630
|
|
|
2
|
Circuit resistance at lowest rated contact force
|
mW
|
≤35
|
|
|
3
|
Rated short-time withstand current
|
kA
|
12.5
|
|
|
4
|
Rated duration of short-circuit
|
s
|
3
|
|
|
5
|
Rated peak withstand current
|
kA
|
31.5
|
|
|
6
|
Rated short-circuit making Current
|
kA
|
31.5
|
|
|
7
|
Rated active load breaking current
|
A
|
630
|
|
|
8
|
Rated closed-loop breaking current
|
A
|
630
|
|
|
9
|
Rated capacity of no-load transformer
|
KVA
|
1250
|
|
|
10
|
Rated breaking current of cable charging
|
A
|
10
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
MECHANICAL DATA
|
|
|
1
|
Weight of movable parts
|
kg
|
0.5
|
|
|
2
|
Closing force due to bellow and atmosphere
|
N
|
65±20
|
|
|
3
|
Force required to hold contacts open at full stroke
|
N
|
175±35
|
|
|
MECHANICAL REQUIREMENTS
|
|
|
1
|
Clearance between open contacts
|
mm
|
9±1
|
|
|
2
|
Average opening speed(average of first 75% of contact gap)
|
m/s
|
0.8±0.3
|
|
|
3
|
Average closing speed(average of last 30% of contact gap)
|
m/s
|
0.6±0.2
|
|
|
4
|
Rated added external contact final force
|
N
|
700±100
|
|
|
Added external contact force at contact touch point
|
490±40
|
|
|
5
|
Contact bouncing duration at closing operation
|
ms
|
≤3
|
|
|
6
|
Closing and Opening non-simultaneity of three-phase Contacts
|
ms
|
≤2
|
|
|
7
|
Maximum Rebound during opening
|
mm
|
≤2
|
|
|
LIFE
|
|
|
1
|
Storage life
|
years
|
20
|
|
|
2
|
Mechanical endurance
|
Times
|
30000
|
|
|
3
|
Contacts limit erosion
|
mm
|
3
|
|
|
NOTES
|
|
|
Note:
Rated insulation values require external insulation,such as SF6,oil or solid dielectric material etc.
|